Trung tâm báo cháy địa chỉ 2 Loop DETECTOMAT Detect 3004
Chat Zalo hoặc Gọi ngay 0984 104 365 để được tư vấn giá tốt!
Trung tâm báo cháy địa chỉ 2 Loop DETECTOMAT Detect 3004
– Microprocessor controlled fire control panel for the use with the Loop 3000 fire detection system components. Approved to EN 54-2 A1 2006, EN 54-4 A1 2002, A2 2006 and VdS for the use according to VdE 0833.
– Large LCD, 160 x 80 points.
– RS-232 interface for easy programming via DPT-Software.
– Space for 2 modules to connect 126 Loop 3000 fire detection system components per module.
– Up to 128 programmable detector zones.
– Event log memory of up to 500 messages.
– Easy programming of up to 504 connections.
– In accordance to EN 61000-6-3 class B for emissions, so suitable for the use in sensitive areas.
– Option for 2 conventional interface cards for controlling up to 16 conventional zones.
– Extinguishing interface for controlling extinguishing and gas suppression systems in accordance to EN 12094.
– Integrated interface for the connection of up to 63 additional network components.
– Integrated control of extinguishing systems via the standard extinguishing interface in accordance to VdS.
Thông số ky thuật
Model | Detect 3004 |
Supply Voltage | 230 VAC (-15% / +10%) |
Emergency Supply | 2 x 12V/12 Ah |
Power Supply | 24 VDC/ 72W/ 3,5A; 1 output 24 VDC/ 800mA for external devices |
Quiescent Current | 250 mA |
Input | 3 inputs for collective evetnts |
Display | LC-display 160 x 80 pixel. Backlit |
Interfaces | RS-232, Bitbus (RS-485 based), Fire brigade interface |
Protection class | IP30 |
Ambient temperature | -5°C to +40°C |
Humidity | 5% to 95% (not condensing) |
Dimensions (H x B x T) | 490 mm x 420 mm x 150 mm |
Weight | 12 kg without batteries |
Material | Sheet metal |
Colour | light grey RAL 7035 |
– Bảo hành: 12 tháng.