Trung tâm báo cháy 16 kênh ZETA PMP16
Chat Zalo hoặc Gọi ngay 0984 104 365 để được tư vấn giá tốt!
Liên hệ
Trung tâm báo cháy 16 kênh ZETA PMP16
– The Premier M Plus control panels are designed to fulfil the requirements of EN54 parts 2 & 4 as well as being easy to install, operate and maintain.
– 4 Common sounder circuits (150mA each).
– Optional add-on zonal sounder circuits (50mA Max.).
– Serial repeater output.
– Auxiliary supply (29 Volts, 250mA).
– Zone & sounder disablement facility.
– Sounder delay facility.
– Zonal to common timer (when fitted with zonal sounder boards).
– One man test mode.
Thông số kỹ thuật và tính năng
Model | PMP16 |
Detection Zones | 16 |
Mains Voltage | 230V AC +10% / -15% @ 50/60 Hz |
System Voltage | 24V DC (nominal) |
Zone Voltage | 21V DC |
Sounder Alarm Output | 4 x 150mA @ 24V DC |
Fault Relay Output | 1 x relay SELV @ 1A maximum |
Fire Relay Output | 1 x relay SELV @ 1A maximum |
Zone Capacity | 32 Devices |
Sounder Activation Delay | 0 – 9 minutes in 1 minute increments |
Zone End Of Line | IN4002 Diode |
Sounder End Of Line | 10KΩ Resistor |
Charger Voltage | 28.4V DC (batteries disconnected) |
Zone Short Circuit Protection | 100mA |
Charger Short Circuit Protection | Batteries less than 20V |
Charger Size | 3.0 Amp |
Operating Temperature | 0°C – 50°C |
Enclosure Size | 485 x 477.5 x 125mm |
– Bảo hành: 12 tháng.