– The SFP-5UDE is a five-zone FACP (Fire Alarm Control Panel).

– Listed to UL Standard 864, 9th edition.

– Built-in DACT (Digital Alarm Communicator/Transmitter).

– Style B (Class B) IDC (Initiating Device Circuit): SFP-5UDE -five IDCs.

– Style Y (Class B) NAC (Notification Appliance Circuit)-special application power SFP-5UD-four NACs.

– Notification Appliances may be programmed as

   + Silence Inhibit.

   + Auto-Silence.

   + Strobe Synchronization for System Sensor, Wheelock, Gentex, Faraday, or Amseco devices.

   + Selective Silence (horn-strobe mute).

   + Temporal or Steady Signal.

   + Silenceable or Nonsilenceable.

– 3.0A total system current for SFP-5UDE.

– Optional Trim Ring TR-CE/-B for semi-flush mounting.

– 24 volt operation.

– Low AC voltage sense.

– Alarm Verification.

– PAS (Positive Alarm Sequence).

– Automatic battery trickle charger.

– Optional Remote Annunciator N-ANN-80.

– Optional Remote Printer Gateway N-ANN-S/PG.

– Optional LED Annunciator Driver N-ANN-I/O.

– Optional 4XTM module (conventional reverse polarity/city box transmitter).

Thông số kỹ thuật

Model  SFP-5UDE
System Capacity Annunciators: 8
Electrical Specifications  Power Supply: 240VAC, 50/60HZ, 0.54A
 
Cabinet Specifications

– Door: 19.26′ (48.92 cm.) high x 16.82′ (42.73 cm.) wide x 0.72′ (1.82 cm.) deep

– Backbox: 19.00′ (48.26 cm.) high x 16.65′ (42.29 cm.) wide x 5.25′ (13.34 cm.) deep;

– Trim Ring (TR-CE): 22.00′ (55.88 cm.) high x 19.65′ (49.91 cm.) wide

Shipping Specifications

Dimensions

– 20.00′ (50.80 cm.) high
– 22.5′ (57.15 cm.) wide
– 8.5′ (21.59 cm.) deep

Temperature and Humidity Ranges This system meets NFPA requirements for operation at 0-49°C/32-120°F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the
useful life of the system’s standby batteries and the electronic
components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that
this system and its peripherals be installed in an environment
with a normal room temperature of 15 – 27°C/60 – 80°F. 
Agency Listings and Approvals The listings and approvals below apply to the basic SFP-5UD
and SFP-10UD control panels. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status.
NFPA Standards  The SFP-5UD(E)  complies with the following NFPA 72 Fire Alarm Systems requirements:
– LOCAL (Automatic, Manual, Waterflow and Sprinkler
Supervisory).
– AUXILIARY (Automatic, Manual and Waterflow) (requires
4XTM).
– REMOTE STATION (Automatic, Manual and Waterflow)
(Where a DACT is not accepted, the alarm, trouble and
supervisory relays may be connected to UL 864 listed
transmitters. For reverse polarity signaling of alarm and
trouble, 4XTM is required.)
– PROPRIETARY (Automatic, Manual and Waterflow).
– CENTRAL STATION (Automatic, Manual and Waterflow,
and Sprinkler Supervised).