Tủ trung tâm báo cháy 4 Loop NITTAN NFU-7000
Chat Zalo hoặc Gọi ngay 0984 104 365 để được tư vấn giá tốt!
Tủ trung tâm báo cháy 4 Loop NITTAN NFU-7000
– Nittan’s SPERA NFU-7000 Network Fire Alarm Control Panel offers modular components to meet a wide variety of applications. Designed for peer-to-peer network communications, the NFU-7000 allows for a maximum of 63 nodes, while providing reliability, flexibility and expandability.
Fire Alarm Control
– One driver card capable of 2 loops is equipped as standard.
– NFU-7000 has capability of three driver cards storage (max 6 loops).
– One loop supports 254 addresses which can be wired in Class A (Style 6 or 7) or Class B (Style 4).
– Use of shielded cable is not required for SLC loops.
– Modular design.
– Four Class A/B (Style Z/Y) Notification Appliance Circuits rated at 1.7 Amps each.
– One Auxiliary power supply, rated at 1.7 Amps for 24 VDC and one resettable 4-wire power supply.
– Large 16 line x 40 character Back-lit LCD Display with user friendly menu.
– Programmable Switch Inputs which allow for multifunctional outputs.
– Four Status Queues with selector switches and LEDs for Alarm, Supervisory, Trouble and Monitor.
– Auxiliary relay contacts for Common Alarm, Common Supervisory and Common Trouble.
– RS-232 port for remote system printer.
– Two Event History Logs comprised of a 1000 alarm history log for alarm related events and a 6000 event history log for all events.
– Supports three configuration files (current, previous and next configuration) with “hot swap” support.
– Supports Conventional Hardwire Adder Modules.
– Built-in One Man Walk Test operation.
– Provides drift compensation for photoelectric smoke detectors.
– Capability to adjust sensitivity levels of intelligent smoke detectors.
– Real time 3D graphical monitoring and control by Nittan’s NFU-Graphic-monitor.
– BACnet support.
– Supports Boolean logic functions.
– Built-in Ethernet port.
– UL listed for Smoke Control.
– Manual Control Function.
– Input Simulation Function.
– Multiple group bypass function with built-in false alarm prevention technology
+ Network Node Bypass;
+ Node Outputs Bypass;
+ Input Zone Bypass;
+ Relay Disconnect;
+ Device/Circuit Bypass.
Network Features
– Up to 63 panels.
– Peer-to-peer network communications.
– Mutual surveillance/ 2 way control available.
– Class A (Style 6 or 7) or Class B (Style 4) wiring configuration.
– ARCNET protocol.
– Supports copper and/or fiber optic network cable.
– Bảo hành: 12 tháng.